ASTM D4185 Standard Practice for Measurement of Metals in Workplace Atmospheres by Flame Atomic Absorption Spectrophotometry
 
ASTM D4185燃燒原子吸收光譜測(cè)定法對(duì)工作場(chǎng)所空氣中金屬的測(cè)定用標(biāo)準(zhǔn)規(guī)范
The health of workers in many industries is at risk through exposure by inhalation to toxic metals. Industrial hygienists and other public health professionals need to determine the effectiveness of measures taken to control workers' exposures, and this is generally achieved by making workplace air measurements. Exposure to some metal-containing particles has been demonstrated to cause dermatitis, skin ulcers, eye problems, chemical pneumonitis, and other physical disorders (1).
AAS is capable of quantitatively determining most metals in air samples at the levels required by federal, state, and local occupational health and air pollution regulations. The analysis results can be used for the assessment of workplace exposures to metals in workplace air.
1. Scope
1.1 This practice covers the collection, dissolution, and determination of trace metals in workplace atmospheres, by flame atomic absorption spectrophotometry.
1.2 The sensitivity, detection limit, and optimum working concentration for 23 metals are given in Table 1.
1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. (Specific safety precautionary statements are given in Section 9.)
TABLE 1 AAS Instrumental Detection Limits and Optimum Working Concentration for 23 Metals
 
Element
Detection Limit, μg/mL
(approximately three times
standard deviation of blank)A
Optimum Linear Range
Upper Limit,
μg/mL
TLV, mg/m3 (elements, compound classes, and oxides)B
 
Ag
0.001
5
0.1 (metal) 0.01 (soluble compounds as Ag)
 
Al
0.04
50
2.0 (soluble salts and alkyls not otherwise classified) 10 (metal dust and oxide)
 
 
 
 
5 (pyro powder and welding fume)
 
Ba
0.01
10
0.5 (soluble compounds)
 
Bi
0.03
10
No Limit expressed for this element
 
Ca
0.002
1
2 (oxide as CaO)
 
Cd
0.0008
1
0.01 (elemental and compoundstotal dust)
 
 
 
 
0.002 (elemental compoundsrespirable fraction)
 
Co
0.009
5
0.02 (elemental and inorganic) 0.1 (carbonyl and hydrocarbonyl)
 
Cr
0.003
5
0.5 (metal and Cr III compounds) 0.05 (water soluble Cr VI compounds)
 
 
 
 
0.01 (insoluble Cr VI compounds)
 
Cu
0.002
5
0.2 (fume) 1 (dust and mists as Cu)
 
Fe
0.005
5
5 (iron oxide fume) 5 (soluble salts as Fe)
 
In
0.03
50
0.1 (metal and compounds)
 
K
0.003
1
No Limit expressed for this element
 
Li
0.0008
1
No Limit expressed for this element
 
Mg
0.0002
0.5
10 (as MgO fume)
 
Mn
0.002
5
0.2 (elemental and inorganic compounds)
 
Na
0.0003
0.5
No Limit expressed for this element
 
Ni
0.006
5
0.05 (elemental, soluble and insoluble compounds)
 
Pb
0.02
10
0.15 (inorganic compounds, fume, dust)
 
Rb
0.003
5
No Limit expressed for this element
 
Sr
0.003
5
No Limit expressed for this element
 
Tl
0.02
50
0.1 (soluble compounds)
 
V
0.06
100
0.05 (pentoxide, respirable dust or fume, as V2O5)
 
Zn
0.002
1
10 (oxide dust as ZnO) 5 (oxide fume as ZnO)
A These detection limits represent ideal laboratory conditions; variability due to sampling, digestion, reagents, and sample handling has not been taken into account.
B Threshold Limit Values of Airborne Contaminants and Physical Agents adopted by ACGIH for 1994–1995. Values are elemental concentrations except as noted.

2. Referenced Documents (purchase separately)
ASTM Standards
D1193 Specification for Reagent Water
D1356 Terminology Relating to Sampling and Analysis of Atmospheres
D1357 Practice for Planning the Sampling of the Ambient Atmosphere
D3195 Practice for Rotameter Calibration
D5337 Practice for Flow Rate Calibration of Personal Sampling Pumps
D7035 Test Method for Determination of Metals and Metalloids in Airborne Particulate Matter by Inductively Coupled Plasma Atomic Emission Spectrometry (ICP-AES)
Index Terms
air monitoring; atomic absorption spectrophotometry; metals; sampling and analysis; spectrometry; workplace air: FAAS (flame atomic absorption spectrometry); Filters/filter procedures--atmospheric analysis; Metal content; Metals and metallic materials; Spectrophotometry--atomic absorption; Workplace air/atmospheres;

  詳情請(qǐng)咨詢
  防火資源網(wǎng)-阻燃防火測(cè)試中心
  電話:(+86)0592-5056213
  傳真:(+86)0592-5105807
  郵件:firetest@firetc.com

凡注明"防火資源網(wǎng)"的所有作品,由<防火資源網(wǎng)>整理編輯,任何組織未經(jīng)<防火資源網(wǎng)>及其擁有者授權(quán),不得復(fù)制、轉(zhuǎn)載、摘編或利用其它方式應(yīng)用于任何商業(yè)行為。

 
 
[ 防火測(cè)試中心搜索 ]  [ ]  [ 告訴好友 ]  [ 打印本文 ]  [ 關(guān)閉窗口 ]  [ 返回頂部 ]

 

 
 
推薦防火測(cè)試
推薦圖文
點(diǎn)擊排行
 
 
網(wǎng)站首頁(yè) | 廣告服務(wù) | 關(guān)于我們 | 聯(lián)系方式 | 服務(wù)協(xié)議 | 版權(quán)聲明 | 網(wǎng)站地圖 | 友情鏈接 | 網(wǎng)站留言 | 舊版本 | 閩ICP備09009213號(hào)
?2019-2021 FIRETC.COM All Rights Reserved ? 備案號(hào):閩ICP備09009213號(hào)-1在線客服 點(diǎn)擊QQ交談/留言 點(diǎn)擊QQ交談/留言