ASTM D5288使用多電極材料測定電絕緣材料追蹤攝影系數(shù)標準試驗方法

放大字體  縮小字體 發(fā)布日期:2012-02-07   瀏覽次數(shù):183  分享到: 分享到騰訊微博
ASTM D5288使用多電極材料測定電絕緣材料追蹤攝影系數(shù)標準試驗方法
ASTM D5288 Standard Test Method for Determining the Tracking Index of Electrical Insulating Materials Using Various Electrode Materials (Excluding Platinum)
ASTM D5288使用多電極材料測定電絕緣材料追蹤攝影系數(shù)標準試驗方法

Electrical equipment has the potential to fail as a result of electrical tracking of insulating material that is exposed to various contaminating environments and surface conditions. A number of ASTM and other tests have been designed to quantify behavior of materials, especially at relatively high voltages. This method is an accelerated test which at relatively low test voltages, provides a comparison of the performance of insulating materials under wet and contaminated conditions. The Tracking Index—Copper Electrodes test is not related directly to the suitable operating voltage in service.
When organic electrical insulating materials are subjected to conduction currents between electrodes on their surfaces, many minute tree-like carbonaceous paths or tracks are developed near the electrodes. These tracks are oriented randomly, but generally propagate between the electrodes under the influence of the applied potential difference. Eventually a series of tracks spans the electrode gap, and failure occurs by shorting of the electrodes.
As in other tracking test methods, for example, IEC 112 and Test Method D3638, this test method specifies test procedures that are intended to promote the formation of surface discharges which will produce carbon tracks in a reproducible manner. Since these conditions rarely reproduce the actual conditions encountered in service, the results of tracking tests cannot be used to infer either direct or relative service behavior of a material in a specific design application. Tracking tests can be used for screening purposes only. Suitability is verified through testing of the material in actual end use or under conditions that closely simulate actual end use.
The use of copper electrodes in this type of test was developed at the University of Cincinnati, NEMA laboratory. It is felt by the members of the Industrial Laminates Section of NEMA that using copper electrodes gives a more realistic value for a tracking index, related to the resin system used to reinforce the substrate of a laminate. In general, tracking tests made with copper electrodes tend to give lower values than platinum electrodes in the same type of test. It is a fact that copper is more widely used than platinum for electrical conductors.
1. Scope
1.1 This test method was developed using copper electrodes to evaluate the low-voltage (up to 600 V) tracking resistance of materials in the presence of aqueous contaminants.
Note 1—At this time, only industrial laminates have been examined using this method which was developed at the National Manufacturers Electrical Association (NEMA) laboratory located at the University of Cincinnati. It was found that a closer end point (less scatter) was obtained than with platinum electrodes, and materials tested tended to be ranked by resin system.
1.1.1 It is acceptable to consider other electrode materials for use with this test method depending upon the application of the insulating material.
1.2 This test method is similar to Test Method D3638, which determines the comparative tracking index of materials using platinum electrodes to produce the tracking on the specimen surface.
1.3 The values stated in metric (SI) units are the standard. The inch-pound equivalents of the metric units are approximate.
1.4 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products, or assemblies under actual fire conditions.
1.5 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests.

2. Referenced Documents (purchase separately)
IEC Publication
IEC112 Recommended Method for Determining the Comparative Track Index of Solid Insulating Materials Under Moist Conditions, 1971 Second Edition
ASTM Standards
D618 Practice for Conditioning Plastics for Testing
D1711 Terminology Relating to Electrical Insulation
D3636 Practice for Sampling and Judging Quality of Solid Electrical Insulating Materials
D3638 Test Method for Comparative Tracking Index of Electrical Insulating Materials
Index Terms
copper electrodes; comparative tracking index; CTI; TI; TI-Cu; track; tracking; tracking; contamination; tracking index; tracking resistance; Comparative tracking index (CTI); Copper electrodes; CTI-CU; Tracking, contamination; Tracking systems; Track resistance--electrical insulating materials;

  詳情請咨詢
  防火資源網(wǎng)-阻燃防火測試中心
  電話:(+86)0592-5056213
  傳真:(+86)0592-5105807
  郵件:firetest@firetc.com

凡注明"防火資源網(wǎng)"的所有作品,由<防火資源網(wǎng)>整理編輯,任何組織未經(jīng)<防火資源網(wǎng)>及其擁有者授權,不得復制、轉(zhuǎn)載、摘編或利用其它方式應用于任何商業(yè)行為。

 
 
[ 防火測試中心搜索 ]  [ ]  [ 告訴好友 ]  [ 打印本文 ]  [ 關閉窗口 ]  [ 返回頂部 ]

 

 
 
推薦防火測試
推薦圖文
點擊排行
 
 
網(wǎng)站首頁 | 廣告服務 | 關于我們 | 聯(lián)系方式 | 服務協(xié)議 | 版權聲明 | 網(wǎng)站地圖 | 友情鏈接 | 網(wǎng)站留言 | 舊版本 | 閩ICP備09009213號
?2019-2021 FIRETC.COM All Rights Reserved ? 備案號:閩ICP備09009213號-1在線客服 點擊QQ交談/留言 點擊QQ交談/留言